Function
- Surge event display, Power quality analysis display (over voltage/under voltage events)
- Rated voltage (3-phase: R-S, S-T, R-T/single-phase: L-N, L-G N-G), Individual leakage current display
- External display connected (RS485 data transmitted) / RS485, Ethernet, Mobile app (Bluetooth)
Specification
- CE certificate, KS certificate, Patents
- High-performance, High-capacity SPD(Total 800, 500, 400, 360, 320, 240kA)
- Full mode protection (Line-Neutral, Line-Ground, Line-Line)
- Performance in compliance with KS C IEC 61643-11
- Surge counter, Over voltage counter, Under voltage counter memory (non-volatile)
- Surge protector diagnosis (Leakage current measurement by phase, Failure indicator, Buzzer)
- Dual safety design (current & thermal fuse)
- Hourmeter (1/10 h) recording and temperature measurement
- Rated voltage measurement (3-phase: R-S, S-T, R-T/single-phase: L-N, L-G N-G)
- Communication function (RS485, Ethernet, Bluetooth)
- Surge Protector information Display (PD Power Meter) (optional)
- Aluminum case for proven safety against surge protector failure
DC 600V/440V/380V/200V
Model
Surge occurrence history display, power quality analysis display (overvoltage, undervoltage), rated voltage display, individual leakage current display, temperature display, hour meter,
Communication function (RS485, Ethernet, Bluetooth)
SPD Type | Class | Surge Current | Phase/Wire | Voltage(AC V) | Connection | Model | Download |
---|---|---|---|---|---|---|---|
Special II | I | Iimp 50kA | 3P 4W | 380 | Parallel | KOP-B-50KI(S2) | Download |
I | Iimp 12.5kA | KOP-B-20KI-KS(S2) | Download | ||||
I | Iimp50kA | 1P 2W | 220 | KOP-A-50KI(S2) | Download | ||
I | Iimp20kA | KOP-A-20KI-KS(S2) | Download | ||||
II | In40kA | 3P 4W | 380 | KOP-B-500K-KS(S2) | Download | ||
II | In20kA | 3P 4W | 380 | KOP-B-400K-KS(S2) | Download | ||
1P 2W | 220 | KOP-A-240K-KS(S2) | Download | ||||
III | Uoc 20KV/10kA | 3P 4W | 380 | KOP-B-400K(S2) | Download | ||
3P 3W | KOP-B-360K(S2) | Download | |||||
1P 2W | 220 | Parallel / Serial | KOP-A-360K(S2) | Download | |||
KOP-A-320K(S2) | Download | ||||||
KOP-A-240K(S2) | Download |
Installation
- Power Line Single-Phase 2-Wire Parallel/Serial
[Model List : KOP-A-240K,320K,360K,240K-KS (Parallel type)KOP-A-240K,320K,360K (Serial type)][Single-Phase Parallel Installation 1]
- Turn off power first.
- Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
- Connect single-phase power Line1, Line2 matching the SPD rated to INPUT L1, L2 terminals.
- Connect the load device to the OUTPUT L1 and L2 terminals.
(Serial-type load current should be less than 10A, Parallel-type load current should be less than 40A; otherwise, Please follow Single-Phase Parallel Installation 2) - Connect earth to the G terminal.
([The length of the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel.) - After the above is done, Supply power to the device.
- If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
- Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage.
- In the case of some Special-Type SPD, if the Line and Neutral wire position changed, an alarm will sound and the warning message “CONNECTION ERROR” will be displayed.
- If Line and Neutral are switched and wired, the alarm is canceled.
- Power Line Single-Phase 2-Wire Parallel
[Model List : KOP-A-20KI-KS,240K,320K,360K,240K-KS, KOP-C-40P, KOP-C-80P, KOP-A-50KI][Single-Phase Parallel Installation 2]
- Turn off power first.
- Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes
- Connect single-phase power Line1, Line2 matching the SPD rated to INPUT L1, L2 terminals
- Connect earth to the G terminal.
(The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel.) - After the above is done, Supply power to the device.
- If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
- Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage..
- In the case of some Special-Type SPD, if the Line and Neutral wire position changed, an alarm will sound, and the warning message “CONNECTION ERROR” will be displayed.
- It will be released after changing the Line and Neutral wire.
* The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.
- Power Line 3-Phase 3-Wire Parallel
[Model List : KOP-B-360K][3-Phase 3-Wire Parallel Installation]
- Turn off power first.
- Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
- Connect 3-phase power R,S,T matching the SPD rated to INPUT L1, L2, L3 terminals.
- Connect earth to the G terminal.
(The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel) - After the above is done, Supply power to the device.
- If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
- Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage...
* The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.
- Power Line 3-Phase 4-Wire Parallel
[Model List: KOP-B-20KI-KS,500K-KS,400K-KS,400K, KOP-B-50KI, KOP-D-40P, KOP-D80P][3-Phase 4-Wire Parallel Installation]
- Turn off power first.
- Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
- Connect 3-phase power R,S,T matching the SPD rated to INPUT L1, L2, L3 terminals. Connect Neutral to the N terminal.
- Connect earth to the G terminal.
(The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50 (maximum). Connect earth to a nearby earthed panel.) - After the above is done, Supply power to the device.
- If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
- Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage...
* The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.
Size
(W)264 x (L)294 x (H)160 KOP-A-50KI, KOP-B-50KI
-
(W)140 x (L)276 x (H)90KOP-B-20KI-KS, KOP-B-500K-KS
-
(W)140 x (L)226 x (H)90KOP-A-20KI-KS
-
(W)140 x (L)216 x (H)90KOP-A-240K-KS, KOP-B-400K-KS, KOP-B-500K-KS
-
(W)140 x (L)190 x (H)90KOP-A-240K, KOP-A-320K, KOP-A-360K, KOP-B-360K, KOP-B-400K