It is a high-quality product that combines perfect protection performance, thorough safety system,
and provision of surge information as a product in which Coenone's know-how and technology are concentrated.

Special Ⅱ type

Surge Protector Surge Protector for Power Special Ⅱ type

KOENONE SURGE PROTECTOR

Power Line Special-Type SPD

Special - Ⅱ type

CAD drawing download360℃ Viewer

Function

  • Surge event display, Power quality analysis display (over voltage/under voltage events)
  • Rated voltage (3-phase: R-S, S-T, R-T/single-phase: L-N, L-G N-G), Individual leakage current display
  • External display connected (RS485 data transmitted) / RS485, Ethernet, Mobile app (Bluetooth)

Specification

  • CE certificate, KS certificate, Patents
  • High-performance, High-capacity SPD(Total 800, 500, 400, 360, 320, 240kA)
  • Full mode protection (Line-Neutral, Line-Ground, Line-Line)
  • Performance in compliance with KS C IEC 61643-11
  • Surge counter, Over voltage counter, Under voltage counter memory (non-volatile)
  • Surge protector diagnosis (Leakage current measurement by phase, Failure indicator, Buzzer)
  • Dual safety design (current & thermal fuse)
  • Hourmeter (1/10 h) recording and temperature measurement
  • Rated voltage measurement (3-phase: R-S, S-T, R-T/single-phase: L-N, L-G N-G)
  • Communication function (RS485, Ethernet, Bluetooth)
  • Surge Protector information Display (PD Power Meter) (optional)
  • Aluminum case for proven safety against surge protector failure
  • VoltageAC 460V/440V/380V/220V/110V
    DC 600V/440V/380V/200V
  • Capacity800KA/500KA/400KA/360KA/320KA/240KA Total
  • Type3-Phase 4-Wire/3-Phase 3-Wire Single-Phase 2-Wire (Serial/Parallel)
  • Model

    Surge occurrence history display, power quality analysis display (overvoltage, undervoltage), rated voltage display, individual leakage current display, temperature display, hour meter,
    Communication function (RS485, Ethernet, Bluetooth)

    SPD Type Class Surge Current Phase/Wire Voltage(AC V) Connection Model Download
    Special II I Iimp 50kA 3P 4W 380 Parallel KOP-B-50KI(S2) Download
    I Iimp 12.5kA KOP-B-20KI-KS(S2) Download
    I Iimp50kA 1P 2W 220 KOP-A-50KI(S2) Download
    I Iimp20kA KOP-A-20KI-KS(S2) Download
    II In40kA 3P 4W 380 KOP-B-500K-KS(S2) Download
    II In20kA 3P 4W 380 KOP-B-400K-KS(S2) Download
    1P 2W 220 KOP-A-240K-KS(S2) Download
    III Uoc 20KV/10kA 3P 4W 380 KOP-B-400K(S2) Download
    3P 3W KOP-B-360K(S2) Download
    1P 2W 220 Parallel / Serial KOP-A-360K(S2) Download
    KOP-A-320K(S2) Download
    KOP-A-240K(S2) Download

    Installation

    • Power Line Single-Phase 2-Wire Parallel/Serial
      [Model List : KOP-A-240K,320K,360K,240K-KS (Parallel type)KOP-A-240K,320K,360K (Serial type)]

      [Single-Phase Parallel Installation 1]

      • Turn off power first.
      • Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
      • Connect single-phase power Line1, Line2 matching the SPD rated to INPUT L1, L2 terminals.
      • Connect the load device to the OUTPUT L1 and L2 terminals.
        (Serial-type load current should be less than 10A, Parallel-type load current should be less than 40A; otherwise, Please follow Single-Phase Parallel Installation 2)
      • Connect earth to the G terminal.
        ([The length of the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel.)
      • After the above is done, Supply power to the device.
      • If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
      • Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage.
      • In the case of some Special-Type SPD, if the Line and Neutral wire position changed, an alarm will sound and the warning message “CONNECTION ERROR” will be displayed.
        - If Line and Neutral are switched and wired, the alarm is canceled.
    • Power Line Single-Phase 2-Wire Parallel
      [Model List : KOP-A-20KI-KS,240K,320K,360K,240K-KS, KOP-C-40P, KOP-C-80P, KOP-A-50KI]

      [Single-Phase Parallel Installation 2]

      • Turn off power first.
      • Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes
      • Connect single-phase power Line1, Line2 matching the SPD rated to INPUT L1, L2 terminals
      • Connect earth to the G terminal.
        (The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel.)
      • After the above is done, Supply power to the device.
      • If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
      • Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage..
      • In the case of some Special-Type SPD, if the Line and Neutral wire position changed, an alarm will sound, and the warning message “CONNECTION ERROR” will be displayed.
        - It will be released after changing the Line and Neutral wire.
        * The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.
    • Power Line 3-Phase 3-Wire Parallel
      [Model List : KOP-B-360K]

      [3-Phase 3-Wire Parallel Installation]

      • Turn off power first.
      • Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
      • Connect 3-phase power R,S,T matching the SPD rated to INPUT L1, L2, L3 terminals.
      • Connect earth to the G terminal.
        (The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel)
      • After the above is done, Supply power to the device.
      • If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
      • Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage...
        * The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.
    • Power Line 3-Phase 4-Wire Parallel
      [Model List: KOP-B-20KI-KS,500K-KS,400K-KS,400K, KOP-B-50KI, KOP-D-40P, KOP-D80P]

      [3-Phase 4-Wire Parallel Installation]

      • Turn off power first.
      • Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
      • Connect 3-phase power R,S,T matching the SPD rated to INPUT L1, L2, L3 terminals. Connect Neutral to the N terminal.
      • Connect earth to the G terminal.
        (The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50 (maximum). Connect earth to a nearby earthed panel.)
      • After the above is done, Supply power to the device.
      • If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
      • Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage...
        * The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.

    Size

    (W)264 x (L)294 x (H)160 KOP-A-50KI, KOP-B-50KI

    • (W)140 x (L)276 x (H)90KOP-B-20KI-KS, KOP-B-500K-KS

    • (W)140 x (L)226 x (H)90KOP-A-20KI-KS

    • (W)140 x (L)216 x (H)90KOP-A-240K-KS, KOP-B-400K-KS, KOP-B-500K-KS

    • (W)140 x (L)190 x (H)90KOP-A-240K, KOP-A-320K, KOP-A-360K, KOP-B-360K, KOP-B-400K