A high-quality product

It is a high-quality product that combines perfect protection performance, thorough safety system,
and provision of surge information as a product in which Coenone's know-how and technology are concentrated.

Special Ⅰ type

Surge Protector Surge Protector for Power Special Ⅰ type

KOENONE SURGE PROTECTOR

Power Line Special-Type SPD

Special - Ⅰ type

CAD drawing download360℃ Viewer

Function

  • Surge Counter
  • Rated voltage (3-phase: R-S, S-T, R-T/single-phase: L-N, L-G N-G), Individual leakage current display
  • External display connected (RS485 data transmitted)

Specifications

  • CE certificate, KS certificate, Patents
  • High-performance, High-capacity SPD (Total 800, 500, 400, 360, 320, 240kA)
  • Full mode protection (Line-Neutral, Line-Ground, Line-Line)
  • Performance in compliance with KS C IEC 61643-11
  • Surge counter memory (non-volatile)
  • Surge protector diagnosis (Leakage current measurement by phase, Failure indicator, Buzzer)
  • Dual safety design (current & thermal fuse)
  • Rated voltage measurement (3-phase: R-S, S-T, R-T/single-phase: L-N, L-G N-G)
  • Communication function
  • Surge Protector information Display (PD Power Meter) (optional)
  • Aluminum case for proven safety against surge protector failure
  • VoltageAC 460V/440V/380V/220V/110V
    DC 600V/440V/380V/200V
  • Capacity800KA/500KA/400KA/360KA/320KA/240KA Total
  • Type3-Phase 4-Wire/3-Phase 3-Wire Single-Phase 2-Wire (Serial/Parallel)
  • Model

    Surge counter, rated voltage display, individual leakage current display

    SPD Type Class Surge Current Phase/Wire Voltage(AC V) Connection Model Download
    Special I I Iimp 12.5kA 3P 4W 380 Parallel KOP-B-20KI-KS(S1) Download
    Iimp 20kA 1P 2W 220 KOP-A-20KI-KS(S1) Download
    II In4 0kA 3P 4W 380 KOP-B-500K-KS(S1) Download
    In 20kA 3P 4W 380 KOP-B-400K-KS(S1) Download
    1P 2W 220 KOP-A-240K-KS(S1) Download
    III Uoc 20KV/10kA 3P 4W 380 KOP-B-400K(S1) Download
    3P 3W KOP-B-360K(S1) Download
    1P 2W 220 Parallel / Serial KOP-A-360K(S1) Download
    KOP-A-320K(S1) Download
    KOP-A-240K(S1) Download

    Installation

    • Power Line Single-Phase 2-Wire Parallel/Serial
      [Model List: KOP-A-240K,320K,360K,240K-KS (Parallel Type) KOP-A-240K,320K,360K (In-Line)]

      [Single-Phase Parallel Installation 1]

      • Turn off power first.
      • Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
      • Connect single-phase power Line1, Line2 matching the SPD rated to INPUT L1, L2 terminals.
      • Connect the load device to the OUTPUT L1 and L2 terminals.
        [Serial-type load current should be less than 10A, Parallel-type load current should be less than 40A; otherwise, Please follow Single-Phase Parallel Installation 2]
      • Connect earth to the G terminal.
        [The length of the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel.]
      • After the above is done, Supply power to the device.
      • If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
      • Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage...
      • In the case of some Special-Type SPD, if the Line and Neutral wire position changed, an alarm will sound and the warning message “CONNECTION ERROR” will be displayed.
    • Power Line Single-Phase 2-Wire Parallel
      [Model List: KOP-A-20KI-KS,240K,320K,360K,240K-KS, KOP-C-40P, KOP-C-80P, KOP-A-50KI]

      [Single-Phase Parallel Installation 2]

      • Turn off power first.
      • Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
      • Connect single-phase power Line1, Line2 matching the SPD rated to INPUT L1, L2 terminals.
      • Connect earth to the G terminal.
        [The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel.]
      • After the above is done, Supply power to the device.
      • If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
      • Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage...
      • In the case of some Special-Type SPD, if the Line and Neutral wire position changed, an alarm will sound, and the warning message “CONNECTION ERROR” will be displayed.
        - It will be released after changing the Line and Neutral wire.
        * The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.
    • Power Line 3-Phase 3-Wire Parallel
      [Model List: KOP-B-360K]

      [3-Phase 3-Wire Parallel Installation]

      • Turn off power first.
      • Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
      • Connect 3-phase power R,S,T matching the SPD rated to INPUT L1, L2, L3 terminals.
      • Connect earth to the G terminal.
        [The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel.]
      • After the above is done, Supply power to the device.
      • If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
      • Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage...
        * The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.
    • Power Line 3-Phase 4-Wire Parallel
      [Model List: KOP-B-20KI-KS,500K-KS,400K-KS,400K, KOP-B-50KI, KOP-D-40P, KOP-D80P]

      [3-Phase 4-Wire Parallel Installation]

      • Turn off power first.
      • Use the 4~5mm bolts to fix the Protector onto the 4 fixing holes.
      • Connect 3-phase power R,S,T matching the SPD rated to INPUT L1, L2, L3 terminals. Connect Neutral to the N terminal.
      • Connect earth to the G terminal.
        [The length sum of the power wire connected to the input terminal and the earth wire for this connection should be less than 50 (maximum). Connect earth to a nearby earthed panel.]
      • After the above is done, Supply power to the device.
      • If the Power Run Lamp is turned on and the Fault Lamp is turned off, the system is normal.
      • Special-type SPD LCD displays Surge Counter, Leakage Current, Voltage...
        * The IEC standard recommends that the length of the earth wire + power wire should be less than 50cm.

    Size

    • (W)140 x (L)276 x (H)90KOP-B-20KI-KS, KOP-B-500K-KS

    • (W)140 x (L)226 x (H)90KOP-A-20KI-KS

    • (W)140 x (L)216 x (H)70KOP-A-240K-KS, KOP-B-400K-KS

    • (W)140 x (L)216 x (H)90KOP-A-240K-KS, KOP-B-400K-KS, KOP-B-500K-KS

    • (W)140 x (L)190 x (H)70KOP-A-240K, KOP-A-320K, KOP-A-360K, KOP-B-360K, KOP-B-400K