Specification
- CE-certified, Patented
- Performance in compliance with KS C IEC standard
- [When 20 kV/10 kA (Voltage 1.2/50 ㎲, Current 8/20 ㎲) is applied, within 150 V-300 V]
- High surge capacity - 200kA/150kA in all, the highest in the world
- LCD surge counter
- [Battery life ≥ 10 years, Replaceable]
- Quadruple hybrid design - first in the world
- Reverse surge protection - first in the world
- Fastening by DIN-rail or Bolt
- Flame-retardant ABS case
[4-Wire Type] 200kA - total / 50kA - mode
4-Wire type : RS422, Dedicated Line Modem Surge Pretection
Model
RTD, RS232 Surge protection
Installation
- Trun off power first.
- Use the Din-Rail or 3-4mm bolts to fix the Protector onto the 2 fixing holes.
- Connect the input or output signal/communication wire to the INPUT I1, I2, I3 and I4 terminals.
- Connect a load device to the OUTPUT O1, O2, O3 and O4 terminals.
(The O1, O2, O3 and O4 are wires connected in series. If these are changed, signal or communication errors may occur.) - Connect earth to the earth terminal.
[The length of the earth wire for this connection should be less than 50cm (maximum). Connect earth to a nearby earthed panel.] - After the above is done, Supply power to the device.